Description
F-bus monitoring module for two fire dampers (BSK).
- Integrated power supply unit, connection for AC 230 V or 24 V BSK versions
- Inputs for BSK feedback OPEN and CLOSED
- Smoke detector inputs for ALARM (lightly soiled, heavily soiled)
- Inputs OPEN, CLOSE and ALARM invertible via configuration software
- Monitoring of running times for direction OPEN/CLOSE
- Limit value specification of the maximum CLOSE running time for both BSKs
- Failure message for both BSK in case of runtime exceedance
- Display of the last CLOSE running time for both BSKs
- Additional activation of runtime monitoring for OPEN function
- Failure evaluation bit-coded via analog data point
- Alarm and bus monitoring with function selection: None, Alarm and Bus, Alarm and BSK On
- Optical status display of operating voltage, F-bus communication and inputs and outputs
- 2× relay (normally open) max. 250 V, 6 A, AC1
- Wiring via PCB terminals with tension clamp connection
- Fast response time by COV (change of value) method
- Replaceable memory chip for the configuration settings
- Firmware update possible during operation via F-bus
Plastic housing for wall and ceiling mounting.