Description
Native BACnet Building Controller (device profile B-BC) according to the BACnet standard ISO 16484-5:2012, Rev. 12, and additionally from firmware version 03.08.08 also BACnet standard ISO 16484-5:2017, Rev. 15.
Freely programmable modular DDC unit with 12“ touch panel and integrated web server functionality for regulation, control, monitoring and optimization of building automation systems.
Realization of simple HVAC solutions up to complex requirements and cross-trade communication with router functionality. A high degree of planning reliability and interoperability is provided by the standardized and widely used communication
protocols, such as BACnet or Modbus.
Significant increase in performance and the number of active participants due to the new F-bus technology.
- Resolution 1280 x 800 pixel
- Visualization and operation via touch
- Pages can be individually shown/hidden
- Freely definable graphics, fault and operating message texts as well as recipe texts (instructions for fault rectification) for each individual fault message
- Individual and collective acknowledgement option of faults, event recording with date and time
- 1× Ethernet interface for network connection and IP communication for BACnet, webservices, Modbus TCP (master/slave), webconfiguration, programming, service, FTP …
- 2× RS485 interface (2-wire) for communication via BACnet MS/TP (with router funktion), Modbus RTU (Master/Slave) and SE-Standard A-, B-, E-bus
- 1× USB service interface (type B) for diagnostics, parameterization and maintenance, webserver functionality
- 2× C-/F-Bus interface, optionally for 22 C-bus or 32 F-bus participants per line
- SD flash card for trend data, application, CAD data, languages, firmware …
- NVRAM for non-volatile data (data retention via battery CR 1632)
- 1× real time clock (RTC) with automatic summer and winter time changeover
Software webconfiguration
- Comfortable password-protected web interface with user-dependent access
- Configuration: Device, network, bus, modem, routing, BACnet settings …
- System: Diagnostic options for BACnet objects, communication, backup & restore, firmware update …
- Project Viewer: Display (and modification) of configured BACnet objects as operating data, alarms and trend recordings …
Further software functions
- Routing of IP and BACnet networks
- Access control via a user administration (roles and rights)
- Compatible to the BACnet standard ISO 16484-5:2012, Rev. 12, and additionally from firmware version 03.08.08 also BACnet standard ISO 16484-5:2017, Rev. 15. Details see PICS list and AMEV test certificate
- Processing of up to 2.000 BACnet objects
- Direct online programming via PC with graphic programming interface, module library and macro functions for compact controls, 65.536 program lines, sample applications are available for individual adaptation
- 32.767 analog and digital data points each (internal), as well as further data points (external) for communication with the RS485 bus, the IO modules and the field bus
- Geographical sun position calculation of the relevant sun angles, as well as the times of sunrise and sunset
- Software package: BACnet G 01 03 10 included
Options, software packages (activation code with registered access via SE homepage)
- Modbus G 01 03 20 (Modbus Master)
Certificates
- BACnet standard ISO 16484-5:2017, Rev. 15 • AMEV test certificate according to DIN EN ISO 16484-5 with AMEV profile AS-B AMEV BACnet 2017 (automation station with extended equipment)
Robust metal housing, front color: black
Front mounting for control cabinet door