Description
Certified native BACnet Advanced Application Controller (device profile B-AAC) according to the BACnet standard ISO 16484-5:2017, Rev. 15.
Freely programmable modular DDC unit for regulation, control, monitoring and optimization of building automation systems. Realization of simple HVAC solutions up to complex requirements and cross-trade communication with router functionality. A high degree of planning reliability and interoperability is provided by the standardized and widely used communication protocols, such as BACnet or Modbus.
Significant increase in performance and the number of active participants due to the new F-bus technology.
- 1× Ethernet interface for network connection and IP communication for BACnet, webservices, Modbus TCP (Client/Server), webconfiguration, programming, service, FTP …
- 2× RS485 interface (2-wire) for communication via BACnet MS/TP (with router funktion), Modbus RTU (Client/Server)
- 1× WLAN and Bluetooth
- 1× EXPANSIONS-Bus F-bus interface via RS 485 physics and up to 4 participants (1 internal, 3 external)
- 12× universal analogue inputs
- 2× digital inputs
- 4× analogue outputs DC 0 … 10V, max. 10 mA
- 8× digital outputs – relay contact (mixed, see data sheet)
- 2× PMW outputs analogue AC/DC 24V, max. 600 mA
- SDHC flash card for trend data, application, CAD data, languages, firmware …
- 1× real time clock (RTC) with automatic summer and winter time changeover
Software webconfiguration
- Comfortable password-protected web interface with user-dependent access
- Configuration: Device, network, bus, modem, routing, BACnet settings …
- System: Diagnostic options for BACnet objects, communication, backup & restore, firmware update …
- Project Viewer: Display (and modification) of configured BACnet objects as operating data, alarms and trend recordings …
Further software functions
- Routing of BACnet networks (B-RTR)
- Supported BACnet Broadcast Management Device (B-BBMD)
- Access control via a user administration (roles and rights)
- Compatible to the BACnet standard ISO 16484-5:2017, Rev. 15. Details see PICS list and AMEV test certificate
- Processing of up to 130 BACnet objects
- Direct online programming via PC with graphic programming interface, module library and macro functions for compact controls, 24.576 program lines, sample applications are available for individual adaptation
- 16.384 analog and digital data points each (internal), as well as further data points (external) for communication with the RS485 bus, the IO modules and the field bus
- Software package: BACnet G 01 03 10 included
- Modbus G 01 03 20 (Modbus Client) included
Certificates
- BACnet standard ISO 16484-5:2017, Rev. 15
- AMEV test certificate according to DIN EN ISO 16484-5
with AMEV profile AS-B AMEV BACnet 2017 (automation
station with extended equipment)
Robust metal housing, industrial design for top hat rail mounting.